Indoor Air Quality-Spectro Analytical Labs Ltd

Regulations and Guidelines pertaining to IAQ
Regulatory Country Standard Ventilation CO2


Regulations and Guidelines pertaining to IAQ
Regulatory Body Country Standard Ventilation CO2
(not exceeding)
OSHA US 29 CFR
1910.1033
(Proposed)
  800ppm
ASHRAE US 62-1989 15 cfm/person
20 cfm/person
7 people/1000ft2
for office
1000 ppm
Codes for new homes/construction
NBCC Canada
Sweden
France
Japan
  0.5 AC/HR
0.5 AC/HR
0.5 AC/HR
15 cfm/person
1000 ppm
1000 ppm
1000 ppm
1000 ppm

Recommended Ventilation rates under the ASHRAE 62-89 standard

Application Ventilation Rate/person Application Ventilation Rate/person
       
Office space 20 cfm Smoking Lounge 60 cfm
Restaurants 20 cfm Beauty Salon 25 cfm
Bars/Cocktail 30 cfm Supermarkets 15 cfm
Hotel Rooms 30 cfm/room Auditorium 15 cfm
Conference Rooms 20 cfm Classrooms 15 cfm
Hospital Rooms 25 cfm Laboratory 20 cfm
Operating Rooms 30 cfm General Retail 15
Source : ASHRAE Standard 62-1989